The T200WLZ1 is a battery powered, wireless thermostat used with the eWL4 Zoning Panel. It communicates call status and zone temperature over a wireless, ISM band, 915 MHz network to the zoning panel.
The thermostat has a large and clear, backlit LCD that displays the indoor temperature, set point temperature, time and operating information. The batteries are changed from the front of the thermostat.
The thermostat has a large and clear, backlit LCD that displays the indoor temperature, set point temperature, time and operating information. The batteries are changed from the front of the thermostat.
Unit of Measure
Specifications
Operation |
N/A Zone thermostat for use with the eWL4 Wireless Zoning panel |
Different Zones |
N/A 4 |
Addresses |
N/A 7 different Addresses to differentiate between neighbors. |
Operating Modes |
N/A Hold Permanent Hold Schedule |
Programmable |
N/A 7 d |
Schedules per Day |
N/A Day Evening Morning Night |
Schedules Format |
N/A 7 d |
System Modes |
N/A Off, Heat, Cool, Auto Heat/Cool, and Emergency Heat when configured as a heat pump. |
1-Zone Operation |
N/A 1-Zone or vacation mode can be selected from the Zone1 thermostat. |
Liquid Crystal Display (LCD) Backlight |
N/A The Liquid Crystal Display (LCD) backlight is turned on whenever a key is pressed. |
Wireless Control |
N/A Uses 915 MHz ISM band with proprietary protocol. Indoor range is over 100 feet. |
Battery Powered |
N/A Uses two AAA Batteries. |
Installer Options
Zone Number |
N/A 1 to 4 |
Factory Setting Zone Number |
N/A 1 |
Home Number |
N/A 1 to 7 |
Factory Setting Home Number |
N/A 1 |
Thermostat Type |
N/A Gas/Electric Horse Power |
Factory Setting Thermostat Type |
N/A Gas Electric |
Heat/Cool Set Point Differential Temperature |
N/A 1 to 6 ºF |
Factory Setting Heat/Cool Set Point Differential Temperature |
N/A 2 ºF |
Stage 1 Differential Temperature |
N/A 1 to 8 ºF |
Factory Setting Stage 1 Differential Temperature |
N/A 1 ºF |
Stage 2 Differential Temperature |
N/A 1 to 8 ºF |
Factory Setting Stage 2 Differential Temperature |
N/A 2 ºF |
Stage 3 Differential Temperature |
N/A 1 to 12 ºF |
Factory Setting Stage 3 Differential Temperature |
N/A 3 ºF |
Stage 4 Differential Temperature |
N/A 1 to 12 ºF |
Factory Setting Stage 4 Differential Temperature |
N/A 4 ºF |
Highest Set Point Temperature |
N/A 50 to 95 ºF |
Factory Setting Highest Set Point Temperature |
N/A 85 ºF |
Lowest Set Point Temperature |
N/A 45 to 95 ºF |
Factory Setting Lowest Set Point Temperature |
N/A 65 ºF |
Minimum off Time |
N/A 0 to 8 min |
Factory Setting Minimum off Time |
N/A 0 min |
Minimum Run Time |
N/A 0 to 8 min |
Factory Setting Minimum Run Time |
N/A 0 min |
Additional Information
Additional Information |
N/A
|