Regulator Diameter |
N/A 160 mm |
Setting |
N/A RDR Ø 80 + 3 cales |
Flow Range |
N/A 15 to 50 m³/h |
Set Flow |
N/A 50 m³/h |
Maximum Temperature |
N/A 60 ºC |
Material |
N/A Galvanized Steel |
Intermediary Step |
N/A 5 m³/h |
Dimension D1 |
N/A 145 mm |
Dimension D2 |
N/A 148 mm |
Dimension L |
N/A 91 mm |
Components |
N/A Air Flow Setting Cale (According to the Air Flow) Piece of Regulation Regulator Casing Screw to Fix the Air Flow Sleave with Lip Seal |
Important |
N/A
|
Presentation |
N/A
The self-adjusting flow regulator RDR can be adjusted on sites according to the requested air flow. The marks on the sides of the opening indicate the settings. |
Adjustment |
N/A
Before setting the regulator, it's necessary to calibrate the flow:
|
Installation |
N/A
The flow regulators are simply fitted into vertical or horizontal ducts. On the horizontal duct, respect the mention «DOWN» indicated at the front of the product. A leap seal ensures the airtightness. When the flow regulator is associated with a diffuser, the minimum distance between the diffuser and the regulator is at least one Ø in extraction mode and 3 Ø in blowing mode. When installing, do not touch the piece of regulation. |
Characteristics |
N/A The curves show the flow variations in m³/h of RDR Ø 150, 160 and 200 mm in extraction according to the difference in of pressure in Pascal (pressure range of 50 to 250 Pa). The values given are averages which may vary of 5 % either way. Flow regulators are characterized by their noise level dB(A). |