- Improves comfort by eliminating overcooling and overheating
- Saves energy by automatically directing over-conditioned air flow to other areas
- Saves energy by reducing air flow to spaces not being used
Unit of Measure
Specifications
Battery Type |
N/A AAA |
Dampers |
N/A WCD Dampers / A80-WL Wireless Actuator |
Operation |
N/A Automatically controls air flow based on temperature setting, space temperature and supply air temperature |
Air Flow Control |
N/A 100% to 0% or minimum air flow set by mechanical stop on the damper actuator. |
Addresses |
N/A 32 different Addresses for different departments, groups or floors. |
Battery Powered |
N/A Used Two AA Batteries |
Damper Operation |
N/A Wireless Thermostat Controlled Air flow |
Damper Close Limit |
N/A Limit closed position to insure minimum air flow when damper is closed. |
Damper Torque |
N/A 80 oz·in |
Temperature Sensor |
N/A Temperature sensor at the WCD damper senses heating or cooling calls. |
Damper Alternating Current (AC) Voltage |
N/A 24 V |
Damper Current |
N/A 2.8 A |
Damper Housing Capacity |
N/A 24 gal |
Damper Housing Material |
N/A Galvanized Steel |
Zones |
N/A 1 zone with up to 32 dampers. |
System Modes |
N/A Off or Auto. In Auto, air flow is controlled by temperature setting. In Off, the air flow is reduced to the preset Off level. |
Schedule Mode |
N/A Programmable start and stop times for daytime operation using automatic air flow control based on temperature setting. |
Hold Mode |
N/A Automatic air flow control based on temperature setting 24/7. |
Liquid Crystal Display (LCD) Backlight |
N/A The Liquid Crystal Display (LCD) backlight is turned on whenever a key is pressed. |
Wireless Control |
N/A Uses 915 MHz ISM band with proprietary protocol. Indoor range is over 100 feet. |
Installer Options
Zone Number |
N/A 1 to 32 |
Factory Setting Zone Number |
N/A 1 |
Home Number |
N/A 1 to 32 |
Factory Setting Home Number |
N/A 1 |
Program Damper Address |
N/A Zone and Home Number |
Deadband Temperature |
N/A 1 to 5 ºF |
Factory Setting Deadband Temperature |
N/A 1 ºF |
Update Interval |
N/A 5 to 30 min |
Factory Setting Update Interval |
N/A 10 min |
Maximum Set Point |
N/A 60 to 90 ºF |
Factory Setting Maximum Set Point |
N/A 80 ºF |
Minimum Set Point |
N/A 55 to 80 ºF |
Factory Setting Minimum Set Point |
N/A 65 ºF |
Damper Factor Per 1 Degree Fahrenheit (ºF) |
N/A 8 to 16 % |
Factory Setting Damper Factor |
N/A 8 % |
Night Air flow |
N/A 0 to 100 % |
Factory Setting Night Air flow |
N/A 50 % |
Off Air flow |
N/A 0 to 100 % |
Factory Setting Off Air flow |
N/A 50 % |
Application
Application |
N/A
|
Features
Features |
N/A
|
Additional Information
Additional Information |
N/A
Install the TS01 Temperature Sensor to detect heating or cooling mode when using the T200WL01 Wireless Thermostat to control air flow The wireless, battery operated thermostat controls the damper/actuator based on the set point temperature, space temperature and the supply air temperature (heating or cooling), The damper is opened or closed proportional to the differential between space and set point temperatures and is continually adjusted to keep the space temperature at the set point. The thermostat can also be used to program the actuator zone and home addresses, This thermostat can also be used for wireless zoning. |